FINITE ELEMENT ANALYSIS OF POWER
CABLE CONNECTION LINE FAULTS UNDER
THE TIME-DOMAIN REFLECTION METHOD
Yuning-Tao*
College of Electrical Engineering and New Energy, China Three Gorges
University, Yichang, Hubei, 443000, China
taoyuning12@163.com
Reception: 12 April 2024 | Acceptance: 6 May 2024 | Publication: 18 June 2024
Suggested citation:
Yuning-Tao (2024). Finite element analysis of power cable connection line
faults under the time-domain reection method. 3C Tecnología. Glosas de
innovación aplicada a la pyme. 13(1), 15-33.
https://doi.org/10.17993/3ctecno.2024.v13n1e45.15-33
https://doi.org/10.17993/3ctecno.2024.v13n1e45.15-33
3C Tecnología. Glosas de innovación aplicadas a la pyme. ISSN: 2254-4143
Ed.45 | Iss.13 | N.1 April - June 2024
15
ABSTRACT
In this paper, finite element analysis of power cable connection line faults based on
the time-domain reflection (TDR) method is designed to improve the accuracy and
efficiency of fault detection. In terms of methodology, a distributed parameter model is
used to describe the cable, and based on the fluctuation equation and characteristic
impedance theory, the impedance characteristics under different fault types are
analyzed. In terms of results, the effectiveness of the method is verified by
mathematical modeling and simulation of single-phase ground faults and
disconnection faults through the Simulink platform in MATLAB. The simulation results
show that in terms of fault localization accuracy, our method controls the error within
0.07m, which is significantly improved compared with the traditional method. In
addition, the fault detection under different noise signals is analyzed, which further
establishes the accuracy of the TDR method in judging different fault types. The TDR-
based power cable fault detection method proposed in this study not only improves
the accuracy of fault localization, but also provides a reliable theoretical basis for the
identification of different types of faults, which contributes to the stable operation and
maintenance of power systems.
KEYWORDS
Time domain reflectometry (TDR), power cable faults, fluctuation equations,
impedance characterization
INDEX
ABSTRACT .....................................................................................................................2
KEYWORDS ...................................................................................................................2
1. INTRODUCTION .......................................................................................................3
2. METHODS ................................................................................................................5
2.1. Fault localization technique based on time-domain reflection method ...............5
2.2. High-precision single cable fault diagnosis method ...........................................7
2.2.1. Reduced time measurement error ...............................................................8
2.2.2. Reduced calibration speed error ...............................................................10
3. RESULTS AND DISCUSSION ................................................................................11
3.1. Power cable connection line fault simulation ....................................................11
3.2. Simulation results analysis ...............................................................................15
4. CONCLUSION ........................................................................................................17
REFERENCES ..............................................................................................................17
https://doi.org/10.17993/3ctecno.2024.v13n1e45.15-33
3C Tecnología. Glosas de innovación aplicadas a la pyme. ISSN: 2254-4143
Ed.45 | Iss.13 | N.1 April - June 2024
16
ABSTRACT
In this paper, finite element analysis of power cable connection line faults based on
the time-domain reflection (TDR) method is designed to improve the accuracy and
efficiency of fault detection. In terms of methodology, a distributed parameter model is
used to describe the cable, and based on the fluctuation equation and characteristic
impedance theory, the impedance characteristics under different fault types are
analyzed. In terms of results, the effectiveness of the method is verified by
mathematical modeling and simulation of single-phase ground faults and
disconnection faults through the Simulink platform in MATLAB. The simulation results
show that in terms of fault localization accuracy, our method controls the error within
0.07m, which is significantly improved compared with the traditional method. In
addition, the fault detection under different noise signals is analyzed, which further
establishes the accuracy of the TDR method in judging different fault types. The TDR-
based power cable fault detection method proposed in this study not only improves
the accuracy of fault localization, but also provides a reliable theoretical basis for the
identification of different types of faults, which contributes to the stable operation and
maintenance of power systems.
KEYWORDS
Time domain reflectometry (TDR), power cable faults, fluctuation equations,
impedance characterization
INDEX
ABSTRACT .....................................................................................................................2
KEYWORDS ...................................................................................................................2
1. INTRODUCTION .......................................................................................................3
2. METHODS ................................................................................................................5
2.1. Fault localization technique based on time-domain reflection method ...............5
2.2. High-precision single cable fault diagnosis method ...........................................7
2.2.1. Reduced time measurement error ...............................................................8
2.2.2. Reduced calibration speed error ...............................................................10
3. RESULTS AND DISCUSSION ................................................................................11
3.1. Power cable connection line fault simulation ....................................................11
3.2. Simulation results analysis ...............................................................................15
4. CONCLUSION ........................................................................................................17
REFERENCES ..............................................................................................................17
https://doi.org/10.17993/3ctecno.2024.v13n1e45.15-33
1. INTRODUCTION
Power cable is an important channel for the transmission of information and power
in the power system, the cable line in the service process will often be subject to
external and internal factors such as damage, such as man-made barbaric
construction, animal bites, high temperature, corrosive gases, liquids, etc., as well as
with the increase in the service time resulting in the aging of the insulation layer of the
surface of the cable and other situations, the above phenomena will be on the
transmission of power and even the entire power grid system security power supply
caused by the important impact [1-3]. All these phenomena will have an important
impact on power transmission and even the safety of the entire power grid system
[1-3]. All-weather monitoring of cables in the core areas or key transmission channels
can greatly improve the safety of the power grid system and reduce the major
economic losses and safety accidents caused by cable failures [4-5].
With the increasing proportion of high-voltage power cables in transmission and
distribution lines, the safety, stability and reliability of their operation have received
widespread attention [6-8]. At present, high-voltage power cables usually use a single-
core structure, this structure of the cable failure, because of its insulation thickness,
the use of metal sheath cross-interconnection wiring mode and the use of cable T-
joints and many other factors, resulting in high-voltage single-core cables than the
10kV three-core cable fault localization is more difficult [9-10].
Cable is an important material and equipment for power system to transmit
information and electric energy. With the rapid development of cities and the
increasing scale of industrial electricity consumption, the safety and reliability of
cables, as an important carrier of information and energy, have been increasingly
emphasized. Literature [11] proposed a novel shape memory alloy (SMA) cable
constrained high damping rubber (SMA-HDR) bearing. It can effectively simplify
bridge design and mitigate cable failures due to potential damage to cables from
strong NF earthquakes. Literature [12] studied the submarine cable detection method
in shallow areas (sea area within 200 meters), and pointed out that Brillouin RF can
be used to detect submarine cables, and the method has no negative impact on
cables. Some discussions on the development and trend of submarine cable detection
technology were also carried out. Literature [13] designed a metal device around the
feeder line, aiming to reduce and minimize the ground fault current generated in the
event of a ground fault in a substation powered by a cable line. The reliability of this
metal device was confirmed by simulation tests. Literature [14] envisions a new type
of zero sequence current filter and ground fault protection relay based on the principle
of cable shielding against ground currents. Numerical tests using PowerFactory
simulation software corroborate the high sensitivity and low number of false trips of
this device. Literature [15] conceived a coordinated protection system designed to
ensure stable operation of the power system even when high temperature
superconducting cables are used, and the feasibility and superiority of the scheme
were corroborated by simulation verification using the PSCAD/EMTDC program.
Literature [16] designed a modified K-means algorithm for feeder selection for full
https://doi.org/10.17993/3ctecno.2024.v13n1e45.15-33
3C Tecnología. Glosas de innovación aplicadas a la pyme. ISSN: 2254-4143
Ed.45 | Iss.13 | N.1 April - June 2024
17
cable network grounding faults to increase the accuracy of feeder selection for full
cable network grounding under various fault conditions. A full cable network model
with five feeders is used for testing and it is proved that this method has high feeder
selection accuracy. Literature [17] discusses the function of distributed temperature
sensor, which is a spatially continuous temperature sensor that measures the
temperature along the cable through a sensing fiber pair. Based on simulation tests
and formula calculations, it is feasible to detect and locate power cable heating faults
using this tool. Literature [18] presents a fast method for detecting and handling faults
inside and on the DC side of a full-bridge bipolar MMC-HVDC line. Electromagnetic
transient simulations corroborate that the above method can exert a positive influence
on transient voltages and current stresses, among others. Literature [19] conceived a
new method for cross-linked polyethylene cable insulation fault detection based on
fiber optic temperature sensors. The distributed fiber optic temperature measurement
technique was operated for insulation degradation test of XLPE pairs of cables, and it
was pointed out that the above method can accurately locate the insulation faults.
Literature [20] proposed a method based on input impedance spectrum to solve the
problem of strong coupling between conductors of 10kv three-core armored cables,
where defects and fault types are difficult to identify. After PSCAD circuit simulation
tests, the results show that the proposed method can effectively identify faults and
local defects in three-core cables. Literature [21] proposes an original algorithm based
on known arc combustion theory to simulate the maximum overvoltage value during
arc combustion. The effect of arc suppression coils on the nature and magnitude of
transient overvoltages and arc excitation overvoltages due to cable insulation
breakdown is investigated. According to the simulation tests on the operation
simulation of different power grids, it is found that the proposed model can clarify the
minimum insulation margin and overvoltage protection trigger threshold of power grid
equipment to ensure the reliable operation of the power grid.
The research idea of this paper is firstly based on the time-domain reflection (TDR)
method, which utilizes the distribution parameter model to characterize the cable
connection line. The impedance characteristics under different fault types are
analyzed by constructing fluctuation equations and characteristic impedance theory.
Subsequently, the Simulink platform in MATLAB is used to conduct simulation
experiments, including the mathematical modeling of single-phase ground faults and
disconnection faults. The effectiveness of the theoretical method is verified by
observing the simulation results. At the same time, the changes in impedance
characteristics of different types of faults are explored, as well as the influence of
noise signals on fault detection. Finally, through data analysis and theoretical
comparison, conclusions are drawn to demonstrate the advantages of this research
method in improving the accuracy and efficiency of fault detection.
https://doi.org/10.17993/3ctecno.2024.v13n1e45.15-33
3C Tecnología. Glosas de innovación aplicadas a la pyme. ISSN: 2254-4143
Ed.45 | Iss.13 | N.1 April - June 2024
18
cable network grounding faults to increase the accuracy of feeder selection for full
cable network grounding under various fault conditions. A full cable network model
with five feeders is used for testing and it is proved that this method has high feeder
selection accuracy. Literature [17] discusses the function of distributed temperature
sensor, which is a spatially continuous temperature sensor that measures the
temperature along the cable through a sensing fiber pair. Based on simulation tests
and formula calculations, it is feasible to detect and locate power cable heating faults
using this tool. Literature [18] presents a fast method for detecting and handling faults
inside and on the DC side of a full-bridge bipolar MMC-HVDC line. Electromagnetic
transient simulations corroborate that the above method can exert a positive influence
on transient voltages and current stresses, among others. Literature [19] conceived a
new method for cross-linked polyethylene cable insulation fault detection based on
fiber optic temperature sensors. The distributed fiber optic temperature measurement
technique was operated for insulation degradation test of XLPE pairs of cables, and it
was pointed out that the above method can accurately locate the insulation faults.
Literature [20] proposed a method based on input impedance spectrum to solve the
problem of strong coupling between conductors of 10kv three-core armored cables,
where defects and fault types are difficult to identify. After PSCAD circuit simulation
tests, the results show that the proposed method can effectively identify faults and
local defects in three-core cables. Literature [21] proposes an original algorithm based
on known arc combustion theory to simulate the maximum overvoltage value during
arc combustion. The effect of arc suppression coils on the nature and magnitude of
transient overvoltages and arc excitation overvoltages due to cable insulation
breakdown is investigated. According to the simulation tests on the operation
simulation of different power grids, it is found that the proposed model can clarify the
minimum insulation margin and overvoltage protection trigger threshold of power grid
equipment to ensure the reliable operation of the power grid.
The research idea of this paper is firstly based on the time-domain reflection (TDR)
method, which utilizes the distribution parameter model to characterize the cable
connection line. The impedance characteristics under different fault types are
analyzed by constructing fluctuation equations and characteristic impedance theory.
Subsequently, the Simulink platform in MATLAB is used to conduct simulation
experiments, including the mathematical modeling of single-phase ground faults and
disconnection faults. The effectiveness of the theoretical method is verified by
observing the simulation results. At the same time, the changes in impedance
characteristics of different types of faults are explored, as well as the influence of
noise signals on fault detection. Finally, through data analysis and theoretical
comparison, conclusions are drawn to demonstrate the advantages of this research
method in improving the accuracy and efficiency of fault detection.
https://doi.org/10.17993/3ctecno.2024.v13n1e45.15-33
2. METHODS
2.1. FAULT LOCALIZATION TECHNIQUE BASED ON TIME-
DOMAIN REFLECTION METHOD
Power cable connection line belongs to a kind of transmission line, in the ideal
case, the cable connection line can be regarded as a uniform transmission line, so it is
feasible to use distribution parameters to describe the cable model. Its equivalent
distribution parameter model in , , , represent the distribution resistance,
inductance, capacitance and conductance per unit length of the transmission line,
respectively.
Its fluctuation equation can be obtained based on the above parameters, which are
obtained:
(1)
The characteristic impedance is the ratio of the incident wave voltage to the
incident wave current , which can be obtained as:
(2)
Among them, the capacitance and inductance are related to the dielectric
constant of the cable, the cross-sectional area of the material core, etc., which
indicates that the wave impedance is different for different kinds of cables.For the
transmission line with small losses, the characteristic impedance can be simplified
to because of ,.The reflection coefficient can
be expressed as follows.
(3)
Where, is the load at the fault point.According to the time interval between the
injection pulse time and the pulse reflection time, the location of the fault point is
calculated as:
(4)
Where, for the pulse propagation speed in the cable medium, and the dielectric
constant of the medium related to , respectively, for the pulse sent to the moment
R
C
G
u
x=Ri +L
i
t= (R+jωL)i
i
x=Gu +Cu
t= (G+jωC)
u
Z0
u
i
Z
0=
u
i=
R+jωL
G+jωC
C
L
Z0
Z0=L/C
ωL>R,ωC>G
ρ=
Z
L
Z
0
ZL+Z0
ZL
L
=
1
2
vρ(t1t2
)
vp
t1,t2
https://doi.org/10.17993/3ctecno.2024.v13n1e45.15-33
3C Tecnología. Glosas de innovación aplicadas a la pyme. ISSN: 2254-4143
Ed.45 | Iss.13 | N.1 April - June 2024
19
and the pulse returned to the launch point of the moment. in the frequency is very
high, the cable in the electromagnetic wave propagation speed tends to a constant
constant.
According to the theory based on time-domain reflection method, we can obtain the
basic characteristics of the impedance of the cable connection line fault as follows.
When the cable is normal, the load impedance and characteristic impedance is
matched, that is,
, then according to the formula (3) reflection coefficient
no reflection echo. at this time the whole section of the cable impedance
uniformity without mutation points, the impedance waveform curve is specifically
expressed as a straight line section of basically unchanged amplitude.
When the cable connection line breakage fault occurs, there is
, then the
reflection coefficient
, the incident wave and the reflection wave has the same
polarity, the incident and reflected voltage waveform shown in Figure 1. at this time,
the cable impedance in the breakage point of a sudden change in the impedance
waveform curve is specifically expressed by the normal impedance waveform, a
sudden increase in the amplitude of a certain location, and tends to be close to
positive infinity. the distance between the point of the mutation and the normal
impedance waveform starting point. The distance between the mutation point and the
starting point of the normal impedance waveform, i.e., the incident/reflected pulse time
difference, and the location of the actual cable connection line short-circuit fault point
to meet the formula
Figure 1. Schematic diagram of incident and reffected waves, when the cable open circuit
occurs
When the cable short-circuit fault, there is
, then the reflection coefficient
. incident and reflected waves of opposite polarity, the incident and
reflected voltage waveforms shown in Figure 2. at this time, the cable impedance in
the short-circuit point of a sudden change in the impedance waveform curve is
specifically manifested by the normal impedance waveform suddenly in a position
of amplitude changes to 0. The mutation point and the normal impedance
waveform starting point of the distance between the distance between that is, the
incident/reflected pulse time difference with the actual cable short-circuit fault point
location to meet the equation (4).
ZLZ0
ρ= 0
ZL=
ρ= 1
ZL= 0
ρ=1
https://doi.org/10.17993/3ctecno.2024.v13n1e45.15-33
3C Tecnología. Glosas de innovación aplicadas a la pyme. ISSN: 2254-4143
Ed.45 | Iss.13 | N.1 April - June 2024
20
and the pulse returned to the launch point of the moment. in the frequency is very
high, the cable in the electromagnetic wave propagation speed tends to a constant
constant.
According to the theory based on time-domain reflection method, we can obtain the
basic characteristics of the impedance of the cable connection line fault as follows.
When the cable is normal, the load impedance and characteristic impedance is
matched, that is, , then according to the formula (3) reflection coefficient
no reflection echo. at this time the whole section of the cable impedance
uniformity without mutation points, the impedance waveform curve is specifically
expressed as a straight line section of basically unchanged amplitude.
When the cable connection line breakage fault occurs, there is , then the
reflection coefficient , the incident wave and the reflection wave has the same
polarity, the incident and reflected voltage waveform shown in Figure 1. at this time,
the cable impedance in the breakage point of a sudden change in the impedance
waveform curve is specifically expressed by the normal impedance waveform, a
sudden increase in the amplitude of a certain location, and tends to be close to
positive infinity. the distance between the point of the mutation and the normal
impedance waveform starting point. The distance between the mutation point and the
starting point of the normal impedance waveform, i.e., the incident/reflected pulse time
difference, and the location of the actual cable connection line short-circuit fault point
to meet the formula
Figure 1. Schematic diagram of incident and reffected waves, when the cable open circuit
occurs
When the cable short-circuit fault, there is , then the reflection coefficient
. incident and reflected waves of opposite polarity, the incident and
reflected voltage waveforms shown in Figure 2. at this time, the cable impedance in
the short-circuit point of a sudden change in the impedance waveform curve is
specifically manifested by the normal impedance waveform suddenly in a position
of amplitude changes to 0. The mutation point and the normal impedance
waveform starting point of the distance between the distance between that is, the
incident/reflected pulse time difference with the actual cable short-circuit fault point
location to meet the equation (4).
ZLZ0
ρ= 0
ZL=
ρ= 1
ZL= 0
ρ=1
https://doi.org/10.17993/3ctecno.2024.v13n1e45.15-33
Figure 2. Schematic diagram of incident and reffected waves, when the cable short circuit
occurs
Cable connection lines occur insulation skin folding, wear and shielding damage,
furthermore, taking into account the on-board cables are usually bundled through the
power center connector connection, where each cable is usually connected through
the contact coupling, the introduction of the connection point will inevitably have an
impact on the test line impedance. this time, there are ,
equivalent to the fault / anomaly for the inductor, capacitor, resistance, series or
parallel connection. At this time, the cable impedance will also undergo a sudden
change, but these states of the electric pulse signal can continue to propagate along
the cable, only part of the signal in the fault/anomaly at the point of reflection, so the
cable impedance after a sudden change can still be restored to a smooth state. the
impedance waveform curve is specifically manifested as a section of the amplitude of
a stable straight line in a certain position amplitude suddenly changed, and then return
to normal, amplitude re The distance between the sudden change point and the
normal impedance waveform start point, i.e., the incident/reflected pulse time
difference, and the actual cable connection line fault/anomaly location also meets the
formula (4).
According to the above analysis, it can be seen that when the cable connection line
short-circuit and disconnection faults occur, the reflected waveform and cable fault
impedance characteristics are obvious, and the impedance test can be used to
directly determine the type of fault, while for other types of faults or anomalies,
although it can be obtained from the characteristics of the change, but for the
judgment of the type of faults or anomalies, the need for more in-depth theoretical
support.
2.2. HIGH-PRECISION SINGLE CABLE FAULT DIAGNOSIS
METHOD
The following analysis of the influencing factors of the positioning accuracy, from
the TDR cable connection line fault location principle considerations, according to the
law of linear superposition of error transfer, can be measured cable fault length l of the
error can be expressed as follows.
ZL0, 1<ρ<1
https://doi.org/10.17993/3ctecno.2024.v13n1e45.15-33
3C Tecnología. Glosas de innovación aplicadas a la pyme. ISSN: 2254-4143
Ed.45 | Iss.13 | N.1 April - June 2024
21
(5)
is the propagation speed of the TDR detection signal in the cable, is the time
interval between the peak of the incident wave and the peak of the reflected wave,
is the wave speed error, and is the time interval measurement error.
The main reason for the existence of the error is mainly due to the measurement
error of the wave speed, as well as the time interval measurement error. positioning
accuracy is the largest positioning error, so in order to improve the positioning
accuracy, the following by reducing the wave speed error and time measurement error
to improve fault location accuracy.
2.2.1. REDUCED TIME MEASUREMENT ERROR
When analyzing the time measurement error of TDR peak point acquisition, when
the sampling rate is certain, the sampling time is determined, and the waveform is
finally recorded as a discrete point. Due to the principle of TDR fault detection, it is
necessary to collect the incident and reflected peak points.When the peak points are
collected by the direct counting method as shown in Fig. 3, the actual collection point
may not be the real peak point, so that there exists a time measurement error, and the
maximum time measurement error meets the formula.
(6)
Figure 3. Schematic diagram of peak extraction by TDR through sampling
Since the system needs to collect the correlated incident wavehead and the
correlated reflected wavehead, there are two samples, so the measurement error of
the whole system satisfies the following equation.
(7)
Δ
l=
1
2
(tΔv+vΔt
)
v
t
Δv
Δt
f
T
Δt
T
2
Δ
t = 2Δt T=
1
f
https://doi.org/10.17993/3ctecno.2024.v13n1e45.15-33
3C Tecnología. Glosas de innovación aplicadas a la pyme. ISSN: 2254-4143
Ed.45 | Iss.13 | N.1 April - June 2024
22
(5)
is the propagation speed of the TDR detection signal in the cable, is the time
interval between the peak of the incident wave and the peak of the reflected wave,
is the wave speed error, and is the time interval measurement error.
The main reason for the existence of the error is mainly due to the measurement
error of the wave speed, as well as the time interval measurement error. positioning
accuracy is the largest positioning error, so in order to improve the positioning
accuracy, the following by reducing the wave speed error and time measurement error
to improve fault location accuracy.
2.2.1. REDUCED TIME MEASUREMENT ERROR
When analyzing the time measurement error of TDR peak point acquisition, when
the sampling rate is certain, the sampling time is determined, and the waveform is
finally recorded as a discrete point. Due to the principle of TDR fault detection, it is
necessary to collect the incident and reflected peak points.When the peak points are
collected by the direct counting method as shown in Fig. 3, the actual collection point
may not be the real peak point, so that there exists a time measurement error, and the
maximum time measurement error meets the formula.
(6)
Figure 3. Schematic diagram of peak extraction by TDR through sampling
Since the system needs to collect the correlated incident wavehead and the
correlated reflected wavehead, there are two samples, so the measurement error of
the whole system satisfies the following equation.
(7)
Δl=1
2(tΔv+vΔt)
v
t
Δv
Δt
f
T
Δt T
2
Δt = 2Δt T=1
f
https://doi.org/10.17993/3ctecno.2024.v13n1e45.15-33
At present, the sampling rate of the prototype of the localizer is 500MHz, and if it is
assumed that there is no error in the propagation speed of the detected signals
calculated by the theory before, it can be calculated that the positioning error is.
(8)
It can be seen that in the center frequency of 60.5MHz, the signal propagation
speed is 500MHz, in the sampling rate of , the positioning error is
within , if you want to continue to reduce the positioning error, you need to
improve the hardware sampling rate, but due to the increase in the hardware sampling
rate caused by the substantial increase in the cost of the hardware, so taking into
account the savings in hardware costs, through the peak extraction algorithm is
studied to reduce the time measurement error and reduce the fault location error.
Therefore, in consideration of saving hardware cost, the peak point extraction
algorithm is used to reduce the time measurement error and fault localization error.
For the cable fault diagnosis signal obtained by the relevant operation in this paper,
the signal sequence is expressed as follows:
(9)
Where is the length of the signal sequence, is the time coordinate of the th
data point, and is the amplitude of the th data point.The principle of this fitting
problem is that for a given signal sequence ,
is the class of functions
consisting of polynomials of all times not exceeding
, and
is found such that:
(10)
The that satisfies the minimum value of in Eq. (10) is called the least
squares fitting polynomial.
The TDR signal waveform can be fitted by a quadratic polynomial, and since the
delay time needs to be obtained by analyzing the incident and reflected waveforms
together, it is necessary to do two quadratic polynomial fits to the incident and
reflected waveforms in the TDR signal. From this, we set the quadratic curve equation
to be.
( 11)
0.207m Δl=
1
2
vΔt0.207
m
2.15 108m /s
±0.215m
(x1,y1),(x2,y2),…,(xi,yi),…,(xN,yN)
N
xi
i
yi
i
(xi,yi)
Φ
m(mN)
P
m(x) =
m
k=0
akxk
Φ
I
=
N
i=1
[Pm(xi)yi]2=
N
i=1
(
m
i=1
akxkyi
)2
Pm(x)
I
p(x) = a0+a1x+a2x2
https://doi.org/10.17993/3ctecno.2024.v13n1e45.15-33
3C Tecnología. Glosas de innovación aplicadas a la pyme. ISSN: 2254-4143
Ed.45 | Iss.13 | N.1 April - June 2024
23
2.2.2. REDUCED CALIBRATION SPEED ERROR
In practice, when fault localization is carried out by TDR on a certain cable
connection, it is necessary to calibrate the speed, and the steps of calibration are as
follows.
1) First take a section of cable of known length l.
2) The calibration method is not known in the case of signal propagation speed,
the first given a signal propagation speed.
3) According to the signal transmission time is the same as the establishment
of the equation, the solution to obtain the true signal propagation speed, the formula
is.
(12)
Where is the real cable length, is the measured cable length, is the real signal
propagation speed, is the given signal propagation speed.
According to Equation (12), the calibrated signal propagation speed can be
calculated as.
( 13)
However, in practice, due to errors in time measurements, it is necessary to add the
time , so that the actual relationship is:
(14)
The exact true speed, then, is.
(15)
Therefore, the velocity error can be calculated according to Eq. (14) and Eq. (15),
obtaining.
(16)
Set . Then the velocity error equation can be expressed as.
l
v
=
l
v
l
l
v
v
v
Calibration =l
v
l
l
v
=
l
v
+Δt
v
=
l
l
v +Δ
t
Δ
v=vCalibration v=l
v
l
l
l
v +Δ
t
l
v
=
t
https://doi.org/10.17993/3ctecno.2024.v13n1e45.15-33
3C Tecnología. Glosas de innovación aplicadas a la pyme. ISSN: 2254-4143
Ed.45 | Iss.13 | N.1 April - June 2024
24
2.2.2. REDUCED CALIBRATION SPEED ERROR
In practice, when fault localization is carried out by TDR on a certain cable
connection, it is necessary to calibrate the speed, and the steps of calibration are as
follows.
1) First take a section of cable of known length l.
2) The calibration method is not known in the case of signal propagation speed,
the first given a signal propagation speed.
3) According to the signal transmission time is the same as the establishment
of the equation, the solution to obtain the true signal propagation speed, the formula
is.
(12)
Where is the real cable length, is the measured cable length, is the real signal
propagation speed, is the given signal propagation speed.
According to Equation (12), the calibrated signal propagation speed can be
calculated as.
( 13)
However, in practice, due to errors in time measurements, it is necessary to add the
time , so that the actual relationship is:
(14)
The exact true speed, then, is.
(15)
Therefore, the velocity error can be calculated according to Eq. (14) and Eq. (15),
obtaining.
(16)
Set . Then the velocity error equation can be expressed as.
l
v=l
v
l
l
v
v
vCalibration =lv
l
l
v=l
v +Δt
v=l
l
v +Δt
Δv=vCalibration v=lv
l l
l
v +Δt
l
v =t
https://doi.org/10.17993/3ctecno.2024.v13n1e45.15-33
(17)
Since the time measurement error satisfies Eq.
(18)
Therefore the range of speed measurement error is.
(19)
According to the above formula, the following conclusions can be drawn, because
is the real speed for a certain value, for the device sampling frequency, ignoring its
error, is also a constant value. t is related to the length of the calibration cable, it can
be seen that when the longer the length of the calibration, the smaller the range of
speed measurement error. by increasing the length of the calibration cable, the
calibration error can be confined to a smaller range to reduce the positioning error.
3. RESULTS AND DISCUSSION
3.1. POWER CABLE CONNECTION LINE FAULT SIMULATION
In this paper, the Simulink simulation platform in MATLAB is used for mathematical
modeling of single-phase ground fault and single-phase disconnection fault of power
cables respectively, and TDR is applied to analyze and process the reflected signals
of the fault point to realize fault ranging of cables, and the feasibility and accuracy of
the TDR on-line detection method and the localization algorithm designed in this
paper are further verified by observing the detection effect under different signal-to-
noise ratios. Accuracy of the TDR on-line detection method and the localization
algorithm designed in this paper.
Due to the complexity of the power system line connection, so in the cable fault
modeling process, to simplify the processing. according to the cable fault type, in
Simulink to find the corresponding module for the connection, when the cable ground
fault occurs, the specific simulation circuit model as shown in Figure 4, which includes
the ranging signal generator module, power supply module, as well as the signal
transmission and fault module, etc. where R indicates the beginning of the matching
resistance, resistance value of 50Ω, C1 for the 3.5 nF insulating capacitance. set the
length of the first cable for 100m, the second cable section length of 500m, the total
length of the line is 600m. in the two sections of the cable to join between the three-
phase fault generator, this time, the cable fault occurs at the location of 100m. the
three-phase power supply module in the figure for the ideal power supply system, the
beginning of the phase is 0 degrees, the operating frequency is 0 degrees, the
Δ
v=
l
t
l
t+Δt
=
l Δt
t
(t+Δt)
=
l
t+Δt
Δt
t
=v
Δt
t
Δt
0
|Δt|
1
f
0
|Δv|
v
t f
f
https://doi.org/10.17993/3ctecno.2024.v13n1e45.15-33
3C Tecnología. Glosas de innovación aplicadas a la pyme. ISSN: 2254-4143
Ed.45 | Iss.13 | N.1 April - June 2024
25
operating frequency is 0 degrees, the operating frequency is 0 degrees. The three-
phase power supply module in the figure is an ideal power system, the starting phase
is 0 degrees, the operating frequency is 20Hz, taking into account the voltage
amplitude in the experimental environment has nothing to do with the detection
method, low-voltage value is more conducive to the graphical observation, so set the
operating voltage of 220V.
Figure 4. Cable grounding fault circuit model
Characteristic parameters of cable connection line include positive sequence and
zero sequence two parts, cable characteristic parameter settings as shown in Table 1,
which are set for the unit resistance, reactance and capacitive reactance of the two
sections of the cable. positive sequence and zero sequence unit length reactance
()
are 0.2016 and 0.3774, respectively. through the three-phase fault generator
to simulate single-phase low-resistance ground faults in cables, just select the phase
A faults in the Fault Generator Parameter Dialog, and set the grounding resistance.
The grounding resistance is set.
Table 1. Cable feature parameter Settings
In order to further verify that the TDR method can complete the detection of
intermittent cable link faults, the fault duration is set to 0.05s. For the test signals, the
frequency of the local cosine carrier signal is
, the corresponding duration
of the m sequence is
, and the period of the sequence is 128. The starting
time of the simulation is 5s, respectively, through the To Workspace module, the
reference signal and the fault signal are outputted to the MATLAB workspace, and
analyzed by the signal processing module. in the process of the simulation, the fault
location can be changed by setting the length of the first section of the cable, and at
the same time, the total length of the cable can be adjusted. in accordance with the
Ω/ km
Rg= 10Ω
Parameter type Positive sequence Zero sequence
Reactance per unit length (Ω/km) 0.2016 0.3774
Reactance per unit length (H/km)
Unit length tolerance (F/km) 0.212 x 10-5
1.2131 ×102
0.2085 ×102
0.112 ×105
f= 10MHz
2×105s
https://doi.org/10.17993/3ctecno.2024.v13n1e45.15-33
3C Tecnología. Glosas de innovación aplicadas a la pyme. ISSN: 2254-4143
Ed.45 | Iss.13 | N.1 April - June 2024
26
operating frequency is 0 degrees, the operating frequency is 0 degrees. The three-
phase power supply module in the figure is an ideal power system, the starting phase
is 0 degrees, the operating frequency is 20Hz, taking into account the voltage
amplitude in the experimental environment has nothing to do with the detection
method, low-voltage value is more conducive to the graphical observation, so set the
operating voltage of 220V.
Figure 4. Cable grounding fault circuit model
Characteristic parameters of cable connection line include positive sequence and
zero sequence two parts, cable characteristic parameter settings as shown in Table 1,
which are set for the unit resistance, reactance and capacitive reactance of the two
sections of the cable. positive sequence and zero sequence unit length reactance
() are 0.2016 and 0.3774, respectively. through the three-phase fault generator
to simulate single-phase low-resistance ground faults in cables, just select the phase
A faults in the Fault Generator Parameter Dialog, and set the grounding resistance.
The grounding resistance is set.
Table 1. Cable feature parameter Settings
In order to further verify that the TDR method can complete the detection of
intermittent cable link faults, the fault duration is set to 0.05s. For the test signals, the
frequency of the local cosine carrier signal is , the corresponding duration
of the m sequence is , and the period of the sequence is 128. The starting
time of the simulation is 5s, respectively, through the To Workspace module, the
reference signal and the fault signal are outputted to the MATLAB workspace, and
analyzed by the signal processing module. in the process of the simulation, the fault
location can be changed by setting the length of the first section of the cable, and at
the same time, the total length of the cable can be adjusted. in accordance with the
Ω/ km
Rg= 10Ω
Parameter type
Positive sequence
Zero sequence
Reactance per unit length (Ω/km)
0.2016
0.3774
Reactance per unit length (H/km)
Unit length tolerance (F/km)
0.212 x 10-5
1.2131 ×102
0.2085 ×102
0.112 ×105
f= 10MHz
2×105s
https://doi.org/10.17993/3ctecno.2024.v13n1e45.15-33
above requirements to complete the parameter settings of the modules, the test
signals are made of m-sequence and cosine signals in accordance with the 1:1 BPSK
modulation, and their waveforms are shown in Fig. 5.
The upper and lower parts of the figure are the waveforms of the m
sequence and
the TDR test signal, respectively. it can be seen that in the same time, the
m
sequence completed 15 reflections, while the TDR test signal reflection amplitude and
number of times than the sequence. The test signal generated by the above is
injected into the cable to be tested through the detection point (D), the test signal and
the normal operation of the cable in the AC signal superposition of the AC signal.
because of the amplitude of the test signal is very small compared to the effective
signal transmission, almost does not have any impact on the normal operation of the
signal transmission, so it is possible to use the TDR to achieve the on-line detection of
cable faults.
Figure 5. The sequence and corresponding TDR test signals
When the test signal in the cable transmission process encounters 100m at the
single-phase ground fault point, will be reflected back, the reflection coefficient and the
impedance value of the fault point of the size of the impedance value is related to the
ground short-circuit fault, the value of the coefficient of -1, the reflected signal and the
test signal is reversed. D point of the original signal collected by the high-pass
filtering, to get the ideal zero-noise environment under the fault signal shown in Fig. 6.
it can be seen that the fault signal in the cable transmission process amplitude
frequency attenuation, from -50~50 (V) amplitude frequency attenuation of -9.63~9.85
(V). It can be seen that the fault signal in the cable transmission process has
amplitude and frequency attenuation, compared with the test signal has a time delay,
the time delay is about
. The amount of time delay is related to the location of
the fault point and the propagation speed of traveling wave in the cable.
2×105s
0.2 ×105
https://doi.org/10.17993/3ctecno.2024.v13n1e45.15-33
3C Tecnología. Glosas de innovación aplicadas a la pyme. ISSN: 2254-4143
Ed.45 | Iss.13 | N.1 April - June 2024
27
Figure 6. Reflected signal at the fault point under ideal conditions
Application of 2.2 chapter described in the high-precision single cable fault diagnosis
method for isolation of fault signals and point C incident signal processing, the output
of the system as shown in Figure 7. in order to facilitate the observation of the results
of the figure has been transformed through the corresponding formula of the
transverse coordinate by the sampling point into the amount of time, the
transformation of the signal with the sampling frequency of the
related to the peak
detection, you can get the relevant waveform peak point, the value of -0.1447, the
corresponding horizontal coordinate is
, that is, the delay time of the
reflected signal is
. From the characteristic parameters of the power
cable. The velocity value of the traveling wave in the cable is estimated
as by the characteristic parameter L and C
of the
power cable, and according to the formula of the cable fault ranging, it can be seen
that the location of the cable fault is about 99.93m away from the detecting point D,
which has an error of 100m from the actual fault. The error is only 0.07 m. Since the
correlation peak is negative, the type of cable fault can be judged accordingly. in the
case of high signal-to-noise ratio, the correlation peak is more obvious, which
indicates that the TDR method can achieve better fault localization with high-precision
single cable fault diagnosis algorithm.
Figure 7. Waveform related to cable grounding faults at a high SNR
f
1.8199 ×105
1.8199 ×105s
v= 1/ LC = 1.6350 ×108m /s
https://doi.org/10.17993/3ctecno.2024.v13n1e45.15-33
3C Tecnología. Glosas de innovación aplicadas a la pyme. ISSN: 2254-4143
Ed.45 | Iss.13 | N.1 April - June 2024
28
Figure 6. Reflected signal at the fault point under ideal conditions
Application of 2.2 chapter described in the high-precision single cable fault diagnosis
method for isolation of fault signals and point C incident signal processing, the output
of the system as shown in Figure 7. in order to facilitate the observation of the results
of the figure has been transformed through the corresponding formula of the
transverse coordinate by the sampling point into the amount of time, the
transformation of the signal with the sampling frequency of the related to the peak
detection, you can get the relevant waveform peak point, the value of -0.1447, the
corresponding horizontal coordinate is , that is, the delay time of the
reflected signal is . From the characteristic parameters of the power
cable. The velocity value of the traveling wave in the cable is estimated
as by the characteristic parameter L and C of the
power cable, and according to the formula of the cable fault ranging, it can be seen
that the location of the cable fault is about 99.93m away from the detecting point D,
which has an error of 100m from the actual fault. The error is only 0.07 m. Since the
correlation peak is negative, the type of cable fault can be judged accordingly. in the
case of high signal-to-noise ratio, the correlation peak is more obvious, which
indicates that the TDR method can achieve better fault localization with high-precision
single cable fault diagnosis algorithm.
Figure 7. Waveform related to cable grounding faults at a high SNR
f
1.8199 ×105
1.8199 ×105s
v= 1/ LC = 1.6350 ×108m /s
https://doi.org/10.17993/3ctecno.2024.v13n1e45.15-33
3.2. SIMULATION RESULTS ANALYSIS
The noise signals with different center wavelengths of TDR are used to detect the
faults of different branches at the same time, and the simulation results are shown in
Fig. 8, in which Fig. 8(a) shows the experimental results of detecting the faults of
63.60 m with the noise signals with the center wavelength of 1472.47 nm. The
correlation peak in the 0 position is used as the reference peak of the measurement,
and indicates the zero point of the measurement. The distance of the second highest
correlation peak relative to the reference peak indicates the location of the break fault,
and it is accurately located at 63.60 m. In addition, the two small peaks on the right
side are caused by the reflected harmonics of the second (2nd refl) and the third (3nd
refl) of the break fault.Fig. 8(b) sets up a short-circuit fault in the cable to be measured
at 63.60 m, and the noise signal with the center wavelength of 1473.22 nm is used as
the detected signal of the branch. It can be seen that there is a correlation peak at
63.60m, and it is negative (-158.45), indicating that a short-circuit fault has occurred
there.
Figure 8. Detection results of cable faults on different cable branches
https://doi.org/10.17993/3ctecno.2024.v13n1e45.15-33
3C Tecnología. Glosas de innovación aplicadas a la pyme. ISSN: 2254-4143
Ed.45 | Iss.13 | N.1 April - June 2024
29
Fig. 8(c) shows the results of impedance mismatch fault detection using a noise
signal with a center wavelength of 1474.75 nm. The impedance mismatch fault on the
cable to be tested consists of a coaxial cable connector (BNC) connection point and
an impedance tunable termination load, and the impedance values of the termination
load are set to be 300, 200, 150, 50, and 0 Ω (short-circuit), respectively. Since the
correlation peak in the disconnected state indicates total reflection, normalizing the
peak there, the correlation peaks of the rest of the curve at the impedance mismatch
indicate the actual reflection coefficients, which are 0.534, 0.338, 0.212, and -0.357,
respectively, and therefore, according to the curves, the impedances at the
impedance mismatches are 173±8, 157±6, 83±11, and 27±3 Ω
. Similarly, the
reflection coefficients and impedance values of the BNC connections are measured
as Similarly, the reflection coefficient and impedance value of the BNC connection
point can be measured as 0.0022 and 59±4Ω, respectively.
In the simulation experiment, the relative error is used to measure the
measurement accuracy, and the relative error is expressed as follows.
Where, x represents the actual measurement value of the length of power cable,
represents the standard length of cable, which is agreed to be the nominal value of
the cable under test. different lengths of cable were measured several times, and the
polynomial fitting of the relative error results of different lengths were obtained, as
shown in Fig. 9. it can be seen that in the measurement range of 100m, the relative
error is around 1%, with the increase of the length of measurement, the relative error
gradually increases, and in the measurement range of 700m, the relative error is
controlled within the range of 3.73%. It can be seen that in the measurement range of
100 m, the relative error is around 1%, and with the increase of the measurement
length, the relative error increases gradually, and in the measurement range of 700 m,
the relative error is controlled in the range of 3.73%, which proves that the TDR
method can be used for the online detection of cable faults, and it has high efficiency
and low error.
Figure 9 Relative error changes with measurement distance
Er
E
r=
|xa|
a
×100
%
https://doi.org/10.17993/3ctecno.2024.v13n1e45.15-33
3C Tecnología. Glosas de innovación aplicadas a la pyme. ISSN: 2254-4143
Ed.45 | Iss.13 | N.1 April - June 2024
30
Fig. 8(c) shows the results of impedance mismatch fault detection using a noise
signal with a center wavelength of 1474.75 nm. The impedance mismatch fault on the
cable to be tested consists of a coaxial cable connector (BNC) connection point and
an impedance tunable termination load, and the impedance values of the termination
load are set to be 300, 200, 150, 50, and 0 Ω (short-circuit), respectively. Since the
correlation peak in the disconnected state indicates total reflection, normalizing the
peak there, the correlation peaks of the rest of the curve at the impedance mismatch
indicate the actual reflection coefficients, which are 0.534, 0.338, 0.212, and -0.357,
respectively, and therefore, according to the curves, the impedances at the
impedance mismatches are 173±8, 157±6, 83±11, and 27±3 Ω. Similarly, the
reflection coefficients and impedance values of the BNC connections are measured
as Similarly, the reflection coefficient and impedance value of the BNC connection
point can be measured as 0.0022 and 59±4Ω, respectively.
In the simulation experiment, the relative error is used to measure the
measurement accuracy, and the relative error is expressed as follows.
Where, x represents the actual measurement value of the length of power cable,
represents the standard length of cable, which is agreed to be the nominal value of
the cable under test. different lengths of cable were measured several times, and the
polynomial fitting of the relative error results of different lengths were obtained, as
shown in Fig. 9. it can be seen that in the measurement range of 100m, the relative
error is around 1%, with the increase of the length of measurement, the relative error
gradually increases, and in the measurement range of 700m, the relative error is
controlled within the range of 3.73%. It can be seen that in the measurement range of
100 m, the relative error is around 1%, and with the increase of the measurement
length, the relative error increases gradually, and in the measurement range of 700 m,
the relative error is controlled in the range of 3.73%, which proves that the TDR
method can be used for the online detection of cable faults, and it has high efficiency
and low error.
Figure 9 Relative error changes with measurement distance
Er
Er=|xa|
a×100%
https://doi.org/10.17993/3ctecno.2024.v13n1e45.15-33
4. CONCLUSION
In this study, we have achieved remarkable research results for the finite element
analysis of power cable connection line faults by the time-domain reflection (TDR)
method. Through simulation experiments, we found that the TDR method can
effectively reflect the change of cable impedance in the case of single-phase ground
faults and disconnected faults, so as to accurately locate the fault location. The
simulation results show that the error of fault localization is controlled within 0.07m,
which is much better than the traditional method.
In addition, this study also explores the fault detection effect under different noise
signals, and finds that the TDR method is still effective in identifying and localizing
faults even under different signal-to-noise ratio environments. For example, the
location of the break fault detected under the noise signal with a center wavelength of
1472.47 nm is accurate to 63.60 m, which proves the stability and reliability of the
method under different conditions.
The analyzed data show that the relative error is controlled within 1% in a
measurement range of 100m, while in a longer measurement range (e.g. 700m), the
error is still controlled within 3.73%. This result not only confirms the high efficiency of
the TDR method for cable fault detection, but also demonstrates its feasibility for long
distance detection.
The finite element analysis method of TDR based on power cable connection line
faults proposed in this study proves its effectiveness both theoretically and practically.
The method not only improves the accuracy and efficiency of fault localization, but
also provides strong technical support for the safe operation of power systems. This
result has important guiding significance for fault detection and prevention in the
power industry, as well as for future cable design and maintenance.
REFERENCES
1. Tian, Y., Zhao, Q., Zhang, Z., Li, L., & Crossley, P. (2018). Current-phase-comparison-
based pilot protection for normally closed-loop distribution network with underground
cable. International Transactions on Electrical Energy Systems, 28(9), e2733.1-
e2733.19.
2. Akbal, B. (2020). High voltage underground cable bonding optimization to prevent cable
termination faults in mixed high voltage lines.
IET Generation Transmission &
Distribution, 14(20).
3. Li, B., He, J., Li, Y., Li, B., & Wen, W. (2020). High-speed directional pilot protection for
mvdc distribution systems. International Journal of Electrical Power & Energy Systems,
121(6), 106141.
4. Cozza, Andrea. (2019). Never trust a cable bearing echoes: understanding ambiguities
in time-domain reflectometry applied to soft faults in cables.
IEEE Transactions on
Electromagnetic Compatibility.
https://doi.org/10.17993/3ctecno.2024.v13n1e45.15-33
3C Tecnología. Glosas de innovación aplicadas a la pyme. ISSN: 2254-4143
Ed.45 | Iss.13 | N.1 April - June 2024
31
5.
Samet, H., Khaleghian, S., Tajdinian, M., Ghanbari, T., & Terzija, V. (2021). A similarity-
based framework for incipient fault detection in underground power cables.
International
Journal of Electrical Power & Energy Systems, 133(3), 107309.
6. Zhang, Zhihua, Xu, Bingyin, Crossley, Peter, et al. (2018). Positive-sequence-fault-
component-based blocking pilot protection for closed-loop distribution network with
underground cable. International Journal of Electrical Power & Energy Systems.
7.
Cataldo, A., Benedetto, E. D., Masciullo, A., & Cannazza, G. (2021). A new
measurement algorithm for tdr-based localization of large dielectric permittivity
variations in long-distance cable systems. Measurement, 174(5), 109066.
8.
Cerretti, A., D'Orazio, L., Gatta, F. M., Geri, A., Lauria, S., & Maccioni, M. (2023).
Countermeasures for reduction of screen currents due to cross country faults in mv
cable distribution networks. Electric Power Systems Research.
9.
Akbal, B. (2019). Mssb to prevent cable termination faults for long high voltage
underground cable lines. Elektronika ir Elektrotechnika, 25(6).
10.
Bragatto, T., Cerretti, A., D'Orazio, L., Gatta, F. M., Geri, A., & Maccioni, M. (2019).
Thermal effects of ground faults on mv joints and cables. Energies, 12.
11.
Fang, C., Liang, D., Zheng, Y., & Lu, S. (2022). Seismic performance of bridges with
novel sma cable-restrained high damping rubber bearings against near-fault ground
motions. Earthquake Engineering & Structural Dynamics, 51(1).
12.
Chen, Y., Li, X., Cai, C., Wu, C., Zhang, W., & Huang, X., et al. (2021). Submarine cable
detection method based on multisensor communication.
Journal of Sensors(Pt.11),
2021.
13.
Popovi, Ljubivoje, M. (2018). Reduction of the fault current passing through the
grounding system of an h v substation supplied by cable line.
International Journal of
Electrical Power & Energy Systems, 99, 493-499.
14.
Lowczowski, K., Lorenc, J., Andruszkiewicz, J., Nadolny, Z., & Zawodniak, J. (2019).
Novel earth fault protection algorithm based on mv cable screen zero sequence current
filter. Energies, 12(16), 3190-.
15.
Nguyen, T. T., Lee, W. G., Kim, H. M., Yang, H. S., & Sciubba, E. (2020). Fault analysis
and design of a protection system for a mesh power system with a co-axial hts power
cable. Energies, 13(1), 220-.
16.
Wan, Q., Zheng, S., & Shi, C. (2022). Feeder selection method for full cable networks
earth faults based on improved k-means. IET generation, transmission & distribution.
17.
Chen, K., Yue, Y., & Tang, Y. (2021). Research on temperature monitoring method of
cable on 10 kv railway power transmission lines based on distributed temperature
sensor. Energies, 14.
18.
Wenig, S., Goertz, M., Heinisch, M., Beckler, S., Kahl, M., & Suriyah, M., et al. (2018).
Internal converter- and dc-fault handling for a single point grounded bipolar mmc-hvdc
system. Electric Power Systems Research, 161(aug.), 177-187.
19.
Liu, Y., Xiong, H., & Xiao, H. (2022). Detecting xlpe cable insulation damage based on
distributed optical fiber temperature sensing. Optical Fiber Technology, 68, 102806-.
20.
Wang, Y., Zhang, J., Yao, C., & Zhao, H. (2022). A mathematical method for local
defects and faults identification of 10 kv three-core cable based on input impedance
spectrum. IET science, measurement & technology.
https://doi.org/10.17993/3ctecno.2024.v13n1e45.15-33
3C Tecnología. Glosas de innovación aplicadas a la pyme. ISSN: 2254-4143
Ed.45 | Iss.13 | N.1 April - June 2024
32
5. Samet, H., Khaleghian, S., Tajdinian, M., Ghanbari, T., & Terzija, V. (2021). A similarity-
based framework for incipient fault detection in underground power cables. International
Journal of Electrical Power & Energy Systems, 133(3), 107309.
6. Zhang, Zhihua, Xu, Bingyin, Crossley, Peter, et al. (2018). Positive-sequence-fault-
component-based blocking pilot protection for closed-loop distribution network with
underground cable. International Journal of Electrical Power & Energy Systems.
7. Cataldo, A., Benedetto, E. D., Masciullo, A., & Cannazza, G. (2021). A new
measurement algorithm for tdr-based localization of large dielectric permittivity
variations in long-distance cable systems. Measurement, 174(5), 109066.
8. Cerretti, A., D'Orazio, L., Gatta, F. M., Geri, A., Lauria, S., & Maccioni, M. (2023).
Countermeasures for reduction of screen currents due to cross country faults in mv
cable distribution networks. Electric Power Systems Research.
9. Akbal, B. (2019). Mssb to prevent cable termination faults for long high voltage
underground cable lines. Elektronika ir Elektrotechnika, 25(6).
10. Bragatto, T., Cerretti, A., D'Orazio, L., Gatta, F. M., Geri, A., & Maccioni, M. (2019).
Thermal effects of ground faults on mv joints and cables. Energies, 12.
11. Fang, C., Liang, D., Zheng, Y., & Lu, S. (2022). Seismic performance of bridges with
novel sma cable-restrained high damping rubber bearings against near-fault ground
motions. Earthquake Engineering & Structural Dynamics, 51(1).
12. Chen, Y., Li, X., Cai, C., Wu, C., Zhang, W., & Huang, X., et al. (2021). Submarine cable
detection method based on multisensor communication. Journal of Sensors(Pt.11),
2021.
13. Popovi, Ljubivoje, M. (2018). Reduction of the fault current passing through the
grounding system of an h v substation supplied by cable line. International Journal of
Electrical Power & Energy Systems, 99, 493-499.
14. Lowczowski, K., Lorenc, J., Andruszkiewicz, J., Nadolny, Z., & Zawodniak, J. (2019).
Novel earth fault protection algorithm based on mv cable screen zero sequence current
filter. Energies, 12(16), 3190-.
15. Nguyen, T. T., Lee, W. G., Kim, H. M., Yang, H. S., & Sciubba, E. (2020). Fault analysis
and design of a protection system for a mesh power system with a co-axial hts power
cable. Energies, 13(1), 220-.
16. Wan, Q., Zheng, S., & Shi, C. (2022). Feeder selection method for full cable networks
earth faults based on improved k-means. IET generation, transmission & distribution.
17. Chen, K., Yue, Y., & Tang, Y. (2021). Research on temperature monitoring method of
cable on 10 kv railway power transmission lines based on distributed temperature
sensor. Energies, 14.
18. Wenig, S., Goertz, M., Heinisch, M., Beckler, S., Kahl, M., & Suriyah, M., et al. (2018).
Internal converter- and dc-fault handling for a single point grounded bipolar mmc-hvdc
system. Electric Power Systems Research, 161(aug.), 177-187.
19. Liu, Y., Xiong, H., & Xiao, H. (2022). Detecting xlpe cable insulation damage based on
distributed optical fiber temperature sensing. Optical Fiber Technology, 68, 102806-.
20. Wang, Y., Zhang, J., Yao, C., & Zhao, H. (2022). A mathematical method for local
defects and faults identification of 10 kv three-core cable based on input impedance
spectrum. IET science, measurement & technology.
https://doi.org/10.17993/3ctecno.2024.v13n1e45.15-33
21. Varetsky, Y., Gajdzica, M., & Kushka, B. (2022). Study of transient overvoltages on csi
adjustable speed drives under arcing slgf in the industrial cable grid.
Electric Power
Systems Research(Aug.), 209.
https://doi.org/10.17993/3ctecno.2024.v13n1e45.15-33
3C Tecnología. Glosas de innovación aplicadas a la pyme. ISSN: 2254-4143
Ed.45 | Iss.13 | N.1 April - June 2024
33